Honeywell E 3 Series
The E3 Series® from Gamewell-FCI is the most sophisticated, yet customizable and cost-effective fire safety system available. Built around innovative, but proven technology it represents the future of fire alarm control, assisted voice evacuation and mass notification. Designed using a “building block” approach, the E3 Series is a full function fire alarm system easily configurable into a distributed network with advanced voice capability. But only the E3 Series has something more: the added benefi t of broadband technology, allowing complete system integration over just two wires or fiber optic cables.
- 2 to 244 SLCs each supporting 159 sensors, 159 modules and 159 addressable sounder bases (In Styles 4, 6, or 7*)
- 625K baud ARCNET communications using wire, fiber, or mixed configurations for installation flexibility
- High-speed 32 bit processor and 8100 event history log
- Advanced Boolean logic-based programming such as AND, OR, NOT, time delay and calendar functions configurable via computer programming
- Supports up to (16), ASM-16 addressable switch or ANU-48 LED driver modules per ILI-MB-E3/ILI95-MB-E3
- Two Class A, Style Z or Class B, Style Y, notification appliance circuits rated at 2.0 amps. per circuit
- Integral city connection
- Flexible 115,200 baud high speed RS-232 interface
- 40 character user-defined text per device
- 15 LCD-SLP displays/annunciators, 6 LCD-E3 displays/annunciators, 5 LCD-7100/RAN-7100 remote LED annunciators per ILI-MB-E3/ILI95-MB-E3
- UL Listed for smoke control (dedicated and non-dedicated) when properly configured
- FM/UL Listed for Pre-action/Deluge use
- Velociti™ Sensors
- Velociti™ Modules
- XP95 Sensors
- XP95 Modules
- E3 Series Broadband
- ILI-MB-E3: Intelligent Loop Interface-Main Board
- ILI95-MB-E3: Intelligent Loop Interface-Main Board
- ILI-S-E3: Intelligent Loop Interface-Expansion Board
- ILI95-S-E3: Intelligent Loop Interface-Expansion Board
- ANX-SR: Addressable Node Expander-Single Ring
- ANX-MR-FO: Addressable Node Expander-Multi-Ring Fiber Optic
- ANX-MR-UTP: Addressable Node Expander-Multi-Ring Twisted-pair
- LCD-E3: LCD Keypad Display
- LCD-SLP: Color Touch screen display with five programmable switches
- NGA: Network Graphic Annunciator
- RPT-E3-UTP: Network repeater card (Twisted pair) Fiber connections require an FML-E3 or an FSL-E3 card.
- FML-E3: Multi-mode fiber-optic card (Use with RPT-E3-UTP)
- FSL-E3: Single-mode fiber-optic card (Use with RPT-E3-UTP)
- DACT-E3: Digital Alarm Communicator Transmitter
- PM-9: Power Supply Module
- PM-9G: Power Supply Module
- LCD-7100: Remote LCD Display
- RAN-7100: Remote LCD Display
- ANU-48: ANU-48 LED Driver Module
- ASM-16: Addressable Switch Module
LOCATION
121 Independence Ln.
Chalfont, PA 18914
OFFICE Hours
M-F: 8:00 am – 5:00 pm